LX-UVL AX Wizard, Release 2.1.10 ReadMe File, April 17, 2009

Copyright (c) 2009 Johnson Controls Inc.      All Rights Reserved.
==================================================================

The Johnson Controls AX Wizards are client/server applications that 
require software to be installed on EC-BOS AX platforms and on any 
client machine running the Wizards.

This package contains software for the client machine to run the 
Johnson Controls LX-UVL Wizard.

This release is the initial release of the Johnson Controls 
LX-UVL AX Wizard. After Setup the following versions will be 
installed on your computer:

- Johnson Controls LX-UVL Configuration 	Version 2.1.10
- LX-UVL External Interface File		      LXUVL_v110.XIF
- LX-UVL Application Program              LXUVL_v112.APB
- LX-UVL Application Program              LXUVL_v112.NXE

I. Client installation (integrator computer)
============================================

This install procedure must be followed before using the LX-UVL 
AX Wizards. It is intended to any PC computer or laptop from which 
the LX-UVL AX Wizard will be configured.

Requirements : PC / Windows 2000, 2003, XP, Vista

1.  Run the setup LX-UVL Configuration v2.1.10 Setup.exe


II. Wizard initial running Instructions
=======================================

It is required to install the EC-NET-AX support pack 2.1.10 or 
later before using this Wizard. It is recommanded to install the EC-NET-AX support pack 2.7.6 for the feature 
"Reversing normally heat and cool" to work properly.

The Wizard is launched from EC-NET-AX. See the instructions in the 
EC-NET-AX support package.

III.I New Features and Problems fixed (Firmware)
====================================

Version 1.12

	- When the CO2 level is available, the minimum fresh air intake will now modulate between
	  the minimum and maximum fresh air intake setpoints proportionally with the CO2 level.
	- New option to allow the Economizer and the Mechanical cooling to function simultaneously.
	- New option to remove the low mix air temperature limit safety regarding fresh air intake.
	- A new option was added to set the reversing valve action (normaly heat or cool) which 
	  prevent the reversing valve to be ON for a long period of time.
	- The device switches to bypass state when an input configured only as Space Temperature is 
	  shorted. This input must be configured as Standard Thermistor or resistive TransTable.
	- Every user defined timers have a minimum value of five seconds.
	- The OptimumStart function has been simplified.
	- The option for fresh air damper minimum control using air volume has been removed.

Version 1.03

	- The apb is now compatible with the new plastic enclosure controller.
	- Bug fix: In some cases, the optimum start can leave the occupancy state in 
	  unoccupied mode during occupied or standby modes until the occupancy state is 
	  changed. Fixed.
	- Bug fix: When the REVERSING_VALVE is configured and the change over time is null, 
	  if the unit switches from cooling to heating, the reversing valve will stay OFF and 
	  the cooling will stay ON while there is a heating demand. Fixed.
	- Adjusted type 2 and 3 thermistor range (-40 to 150C).

Version 1.02

	- Bug fix: When the REVERSING_VALVE is configured and the change over time is lower
	  than the cooling stage min ON time, the unit could switch from heating to cooling
	  without turning the reversing valve OFF thus staying always ON and heating while 
	  there is a cooling demand. Fixed.
	- Bug fix: After an optimum start has taken effect and the occupancy state is set to 
	  occupied, the unit status will display the morning warmup mode until a heating or 
	  cooling demand takes place. This bug has no internal effects. Fixed.
	- The first cooling stage will wait until the demand has reached 51% instead of75% 
	  after switching from the economizer to the mechanical cooling.

Version 1.01

	- Hardware outputs (analog) can now be configured as 2V to 10V.

   
III.II New Features and Problems fixed (Wizard)
====================================

Version 2.1.10

 - Updated: The XIF file was updated to version 110.
 - Updated: The application program files (APB and NXE) were updated to version 112.
 - Fixed: It was possible to configure Fan_Speed_2 whithout Fan_Speed_1.
 - Fixed: An invalid input configuration selection didn't change back to previous selection.
 - Fixed: Run-time error after changing variable nviOccCmd's type.
 - Fixed: Run-time error and crash when trying to configure a bound or monitored input. 
 - Fixed: Humidity section in PID was Disabled. 
 - Added: It is now available the default input values in ini file and the file is installed in the commonfles folder.
 - Added: Feature "Reversing normally heat and cool"
 - Added: When the CO2 level is available, the minimum fresh air intake will now modulate between
	  the minimum and maximum fresh air intake setpoints proportionally with the CO2 level.
 - Fixed: When configuring floating fresh air damper the CO2 setpoint was grayed out. 
 - Changed: Changing variable name according to the input and output type.
 - Added: New option to remove the low mix air temperature limit safety regarding fresh air intake.
 - Fixed: The application couldn't show up to front. 

Version 2.0.0
	- Initial release.

IV. Known Problems and Workarounds
===================================